Useful tools

How many amps will it draw?

Work out the current a load will draw from its power rating, or the power and kVA from a known current. For DC, single-phase and three-phase circuits.

Calculate
System

Use the voltage between two phases, such as 208 V on a 120/208 V supply or 480 V on a 277/480 V supply.Pick a common voltage or type your own.

Real power, as on the nameplate. If it’s rated in kVA, enter that figure as kW with a power factor of 1.

Measured or nameplate current. On three-phase, the current in each phase.

Use 1 for heaters and other resistive loads. Motors are often 0.8 to 0.9.

Results update as you type.

Result

Current23.15A
Apparent power5.56kVA

A 5 kW load on a 240 V single-phase supply with a power factor of 0.9 draws about 23.15 A.

Real power
5,000 W
Formula
I = P ÷ (V × PF)
Apparent power
kVA = V × I ÷ 1000
Real power4.32kW
Apparent power4.80kVA

A load drawing 20 A from a 240 V single-phase supply with a power factor of 0.9 uses about 4.32 kW (4.80 kVA).

Real power
4,320 W
Formula
P = V × I × PF
Apparent power
kVA = V × I ÷ 1000

How it’s calculated

Power, voltage and current

Power is voltage multiplied by current. On AC circuits the power factor is part of the calculation, and on three-phase circuits so is √3:

DC
P = V × I
Single-phase AC
P = V × I × PF
Three-phase AC
P = √3 × V × I × PF
Apparent power
kVA = V × I ÷ 1000 (× √3 on three-phase)

To find the current, the same formulas are rearranged: I = P ÷ (V × PF) on single-phase, or I = P ÷ (√3 × V × PF) on three-phase. On DC there is no power factor, so kVA and kW are the same.

P
Real power, in watts (1 kW = 1,000 W)
V
Supply voltage. On three-phase, the line-to-line voltage between two phases
I
Current, in amperes. On three-phase, the current in each phase conductor
PF
Power factor, from 0 to 1. Not used on DC
√3
About 1.732, for balanced three-phase loads
kVA
Apparent power. Generators, UPS units and transformers are rated in kVA