Useful tools

Voltage drop calculator.

Check the voltage drop on a circuit before you buy cable — and find the smallest conductor that keeps it within 3%.

Conductor material

Results update as you type.

Result

Voltage drop–V
Percent drop–%

–

Voltage at load
– V
Nominal voltage
– V
Conductor area
– cmil · – mm²
Smallest size for ≤ 3%
–

How it works

How voltage drop is calculated

Every conductor has resistance, so some voltage is lost between the supply and the load. The longer the run and the higher the current, the bigger the drop — and the larger the conductor, the smaller it gets.

This calculator uses the standard approximation used by electricians and cable manufacturers:

VD = (2 × K × L × I ÷ CM) × f

K
Resistivity constant — 12.9 for copper, 21.2 for aluminium (ohm-cmil/ft)
L
One-way circuit length, in feet
I
Load current, in amperes
CM
Conductor cross-section, in circular mils
f
1 for single-phase and DC · 0.866 for three-phase (2 × 0.866 ≈ √3) · 0.5 for line-to-neutral on 3-phase 4-wire