Voltage drop explained: how to choose the right cable size

Why long cable runs lose voltage, how to work it out, and how to choose a conductor that keeps the drop within the common 3% guideline.

Line drawing of a stranded cable cross-section

Every conductor has resistance, so some voltage is always lost between the supply and the load. On a short run you will barely notice it. On a long run, or with a heavy load, too much voltage drop can mean dim lighting, motors that run hot and struggle to start, and equipment that does not perform as it should.

The good news: it is easy to estimate, and the fix is usually a larger conductor.

How voltage drop is calculated

The standard approximation used by electricians and cable manufacturers, and by our voltage drop calculator, is:

VD = (2 × K × L × I ÷ CM) × f

  • K: resistivity constant, 12.9 for copper and 21.2 for aluminium (ohm-cmil/ft)
  • L: one-way length of the circuit, in feet
  • I: load current, in amperes
  • CM: conductor size, in circular mils
  • f: 1 for single-phase and DC, 0.866 for three-phase

A worked example

Take a 20 A load, 100 ft from the panel, on a 120 V single-phase circuit with copper conductors:

Copper conductor Voltage drop Share of 120 V
12 AWG 7.9 V 6.6%
10 AWG 5.0 V 4.1%
8 AWG 3.1 V 2.6%

A common design guideline (an informational note in the US National Electrical Code) is no more than 3% drop on a branch circuit, and 5% for feeder and branch combined. In this example, 8 AWG is the first size that keeps the drop under 3%. On a 240 V circuit the same run loses the same number of volts, but that is only half the percentage.

Good to know

  • Voltage drop is only one check. Conductors must also be rated for the current (ampacity), the temperature and the installation method.
  • Aluminium has higher resistance than copper, so it needs a larger size to keep the same drop.
  • Treat the numbers as planning estimates, and have every installation designed and verified by a qualified electrician.

Work out your own run

Use the voltage drop calculator with your own lengths and loads. It covers copper and aluminium from 18 AWG to 2000 kcmil and shows the minimum size that meets your target. When you know what you need, send us your list for a quote.